3WL Air Circuit Breakers
3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)
General data
22
Siemens · 2012
Data that can be transmitted over the PROFIBUS DP/MODBUS or the Breaker Data Adapter
1)
Data only available in conjunction with the COM15 module (BUS connec-
tion not required).
2)
Only possible with ETU76B.
Available
-- Not available
All 3WL circuit breakers with ETU45B, ETU76B (CubicleBUS integrated)
Transmittable circuit breaker data
BSS BDAPLUS BSS COM15/COM16
Order code (Order No. of circuit breaker + "–Z")
Order No.
F01
+"BDAPLUS"-
Order No.
F02/F12
Potential applications
Transmission of circuit breaker data to PROFIBUS DP or MODBUS and integration into
higher-level visualization systems are possible
e. g. in PCS7, Power Management Systems, WinCC (including add-ons like the text message radio server)
--
Transmission of circuit breaker data and software (i. e. HTML pages with data) to a local output
device, or remotely through Ethernet/Intranet/Internet (without the possibility of integration into
higher-level visualization systems)
e. g. for monitoring, diagnostics, maintenance and parameterization of individual circuit breakers
--
Utilization of the functionality of all CubicleBUS modules
e.g. configuration of the configurable digital output module, status check of the digital input modules,
diagnostics
Transmittable circuit breaker data without integrated measurement function
Device identification
Communication address, Order No., switch in as-delivered state, circuit breaker parameters
(size, number of poles, rated current module etc.), identification numbers, release type,
free text for plant code and comments
--
1
)
Operating states
On/off status message, storage spring, tripped, readiness
Switching position (connected, test and disconnected position, not present) for withdrawable circuit
breakers,
PROFIBUS/MODBUS write protection on/off, free user input
--
1
)
--
1
)
Control commands
Switch circuit breakers ON/OFF, switch free user output ON/OFF
Reset tripped signal
Delete event and history memory
Rest min./max. measured values, reset maintenance information
--
1
)
--
1
)
History
Read out the event protocol, read out the release protocol --
1
)
Information on maintenance
Number of tripping operations - L, S/I and total, contact erosion
Number of switching operations - under load and total, operating hours
--
1
)
Event signals
Tripped signals with data on tripping currents
Alarmsignals (e. g. overload) with incoming/outgoing information
All named event signals with time stamp
--
1
)
--
1
)
Parameterization of protection functions
Readout of protection function parameters
Modification of settings for protection function parameters via communication
Parameter set switchover supported (set A to set B and vice versa)
2
)
2
)
2
)
2
)
Measured values
Phase currents, each with min./max. value
Temperature in the circuit breaker with min./max. value
Temperature in the control cabinet with min./max. value
All named measured values with time stamp
--
1
)
--
1
)
--
1
)
Measurement function Plus
Order code F01+ ... or F02+ ... F05
Additional transmittable circuit breaker data with integrated measurement function
Additional event signals
Threshold value alarms (e. g. over/underfrequency, over/undervoltage)
Parameterization of expanded protection functions and setpoints (threshold values)
Readout of parameters of expanded protection functions
Modification of settings for protection function parameters
Readout and setting of threshold values
Additional measured values
Voltages, powers, energy, p.f., Frequency with min./max. value
Harmonic analysis
Recording of currents and voltages for configurable events in waveform memory
© Siemens AG 2011